DIO 16 CI

DIO 16 CI

Product description

  • Module with 16 digital in- / outputs via CAN bus
  • Analogue input for heating current reading via external current transformers (three phases)
  • Data is cyclically sent via CAN bus and read by all connected controllers
  • Allocation of IO's to control zones through project setup in the controller
  • Use as control outputs, alarms or IOs in Soft PLC
  • Status LEDs for signaling module status and interface operation

Advantages

  • Savings potential from replacing long sensor wiring with de-central structure
  • Little installation effort
  • Easy expansion



Product information

Technical specifications

General Data

Rated voltage18-30 VDC
Power consumption2 W
Fuse protection8 A M
Status displayLEDs
Dimensions(HxWxD in mm) 99 x 22.5 x 114.5
MountingDIN rail (DIN EN 50022)
HousingPlastic, Phoenix ME 22.5 Bus 10/2
Weight0.3 kg
Operating temperature0...55 °C
ConnectionsSpring terminal
Ingress protectionIP20
Addressing modeAuto addressing
StandardsCE, EN 61326-1
Data backupPower failure safe in EEPROM


Data interfaces

CANSeries; protocols: CAN Bus Standard (2.0A), Canopen (Profile CiA 401 V2.01); Baud rate: 250 kBps



Heating current measuring inputs

Quantity1, three-phase, via current transformer
Measurement signal42 mV/A



Digital inputs

Quantity16
Electrical data0-30 VDC, 2.5 mA at 24 VDC


Digital outputs

Quantity16
TypeLogic output, no galvanic isolation, internal free-wheeling diode, short-circuit proof
Electrical data10-30 VDC, 500 mA (per output) at 25 °C


Analogue inputs

Quantity4 (output types and/or measuring range configurable)
TypeU (0...10 VDC resp. 2...10 VDC) | I (0...20 mA resp. 4...20 mA)
Input resistance> 10 kOHM | 120 Ohm
Resolution15 Bit
Sampling rate500 ms
MonitoringLine break (only for 2...10 VDC, respectively 4.20 mA)


Analogue outputs

Quantity4 (output types and/or measuring range configurable)
TypeU (0...10 VDC resp. 2...10 VDC) | I (0...20 mA resp. 4...20 mA)
Resolution12 Bit
Precision0.5 % of final value


Download

In the Media & Downloads section you will find an overview of all product-specific documents. 
For technical data like e.g: User guides, service manuals, etc. please register.

To media & downloads

Accessories

Current transformer, 4 measuring coils, measuring range up to 40A
Summation current transformer, 1 measuring coil, measuring range up to 60A
Current transformer, 1 measuring coil, measuring range up to 200A
Current transformer, 1 measuring coil, measuring range up to 400 A
Current transformer, 4 measuring coils, measuring range up to 40A
Summation current transformer, 1 measuring coil, measuring range up to 60A
Voltage measurement